Riverfront basement, Ahmedabad

The brief

What made this one difficult

Ground water sat 2 m below existing level and never dropped. Dewatering at the volume required would have been refused, so the design had to hold water out rather than pump it away.

Uplift on the raft exceeded the dead load of the completed structure at basement stage.

What we did

The package, step by step

One contractor from the borelog to the final test certificate.

  1. Cut-off wall

    1,000 mm diaphragm wall taken 4 m into the underlying clay to cut the seepage path.

  2. Uplift anchors

    Permanent tension anchors under the raft with double corrosion protection.

  3. Strutting

    Two levels of 800 mm pipe struts, preloaded and released as slabs cast.

  4. Records

    Slurry parameters, cube results and anchor certificates issued weekly to the client.

4 levels

Basement depth

32 m

Wall depth

96

Permanent uplift anchors

< 2 l/min

Total seepage at handover

On site

Photographs from the works

Riverfront basement, Ahmedabad — photograph 1
Riverfront basement, Ahmedabad — photograph 2
Riverfront basement, Ahmedabad — photograph 3
Riverfront basement, Ahmedabad — photograph 4
Riverfront basement, Ahmedabad — photograph 5
Riverfront basement, Ahmedabad — photograph 6

“The wall held water out from day one. We budgeted for continuous dewatering and never switched the pumps on.”